35m 110kV Transmission Tangent Tower - Double Circuit Steel Lattice Structure
Key Features
- 35-meter height steel lattice tower designed for 110kV double-circuit transmission with 350-meter design span
- High-strength Q420/Q460 steel with hot-dip galvanization (85μm zinc coating) ensuring 50-year design life
- ACSR 240 conductor per phase with 60-100 MW power transmission capacity per circuit
- OPGW ground wire with 48-96 fiber optic cores for lightning protection and grid communication
- IEC 60826 and GB 50545 compliant design withstanding 35 m/s wind speed and 15mm ice accretion
Description
SOLARTODO 35m 110kV Transmission Tangent Tower: The Backbone of Regional Power Grids
1. Introduction: Engineering for Grid Stability and Performance
The SOLARTODO 35m 110kV Transmission Tangent Tower is a critical infrastructure component engineered for the high-stakes environment of regional power transmission. As the workhorse of the modern electrical grid, this tangent (or suspension) tower is designed to support dual-circuit 110-kilovolt (kV) lines over vast distances, forming the structural backbone for straight sections of transmission corridors. Representing between 70% and 80% of the structures on a typical high-voltage line, the tangent tower’s efficiency, reliability, and cost-effectiveness are paramount. This specific model, standing at a height of 35 meters, is optimized for a standard design span of 350 meters, carrying one ACSR 240 conductor per phase. It is meticulously designed in compliance with leading international standards, including IEC 60826 and GB 50545, ensuring a 50-year design life with minimal maintenance and maximum operational uptime. Its function is to manage the immense vertical loads imposed by conductor weight and transverse loads from wind, ensuring uninterrupted power delivery under diverse environmental conditions.
2. Structural Design and Material Integrity
The structural integrity of a transmission tower is its most fundamental attribute. The SOLARTODO 35m tower is constructed from high-strength steel lattice, a design proven for its exceptional strength-to-weight ratio and resilience. We utilize Grade Q420 and Q460 steel for primary structural members, offering a yield strength of over 420 MPa. The entire structure undergoes a hot-dip galvanization process, applying a protective zinc coating with a thickness of no less than 85 micrometers (μm), which provides robust corrosion resistance for a design life of 50 years, even in moderately corrosive environments. The tower is designed to withstand a basic wind speed of up to 35 m/s (126 km/h) and radial ice accretion of up to 15 mm, as stipulated by ASCE 10-15 design guidelines. The foundation is a critical interface with the ground, and our designs typically specify a reinforced concrete pile foundation, engineered to achieve a tower footing resistance of less than 10 ohms, a crucial parameter for effective lightning dissipation and system safety. In regions with high lightning activity, this can be enhanced to below 4 ohms.
3. Electrical Configuration and Capacity
This tower is engineered for a double-circuit 110kV application, a common configuration for enhancing grid reliability and power density within a given right-of-way. Each circuit is capable of transmitting approximately 60 to 100 megawatts (MW) of power, depending on operational parameters. The tower supports a single ACSR 240 conductor per phase. The "240" designation refers to the nominal aluminum cross-sectional area of 240 square millimeters. This conductor type, Aluminum Conductor Steel Reinforced (ACSR), is selected for its optimal balance of conductivity, tensile strength, and cost. Its ampacity, or current-carrying capacity, is rated according to the IEEE 738 standard, which allows for dynamic line ratings based on real-time weather conditions. At the apex of the tower, an Optical Ground Wire (OPGW) is installed. This dual-function cable provides shielding for the phase conductors against direct lightning strikes while embedding a high-bandwidth fiber optic core, typically containing 48 or 96 fibers, for grid monitoring, SCADA system communication, and third-party telecommunications revenue.
4. Insulation and Conductor System
Insulation is a critical element in preventing flashovers and ensuring the safety and reliability of the transmission line. The 35m 110kV tower utilizes a suspension insulator assembly, commonly known as an "I-string," which allows the conductor to swing in response to wind, mitigating mechanical stress on the tower structure. Our standard offering includes high-grade porcelain insulators, a time-tested material known for its durability and excellent dielectric properties, with each string typically comprising 8 to 10 discs for a 110kV system. As an alternative, we offer advanced composite polymer insulators, which are up to 70% lighter than their porcelain counterparts, simplifying installation and reducing tower weight. These composite insulators also offer superior performance in polluted environments and high resistance to vandalism. The conductor itself, ACSR 240, is a composite cable with high-purity aluminum strands for conductivity and a high-strength steel core to bear the mechanical tension, which can exceed 30 kilonewtons (kN) under heavy load conditions.
5. Application, Installation, and Maintenance
The 35m 110kV Transmission Tangent Tower is specifically designed for straight-line sections of a transmission route. Its primary role is to suspend conductors, managing vertical and transverse loads, while angle or terminal towers handle the significant tensile loads associated with changes in line direction. With a typical design span of 350 meters between towers, approximately three of these structures are required per kilometer of transmission line. Installation is a highly coordinated process involving foundation construction, tower assembly (often on the ground before being lifted into place by a crane), and finally, conductor stringing. The lattice design facilitates on-site assembly with bolted connections, and a typical 35m tower can be erected by a skilled crew in under 3 days. The 50-year design life is predicated on a structured maintenance program, which includes periodic visual inspections (often conducted by drones), torque checks on bolted connections every 5-10 years, and monitoring of the grounding system’s integrity.
Frequently Asked Questions (FAQ)
1. What is the primary application of this 35m 110kV tangent tower? This tower is designed exclusively for the straight sections of a 110kV transmission line. Its function is to suspend the conductors, managing their weight and wind-induced side loads. It constitutes 70-80% of the towers on a typical line, making it the most common and cost-effective structure for long-distance power transmission corridors where the line does not change direction.
2. What is the expected design life and what maintenance is required? The tower is engineered for a 50-year operational lifespan. This longevity is achieved through the use of high-strength, hot-dip galvanized steel that resists corrosion. Recommended maintenance includes periodic visual inspections every 1-2 years, checking bolt torque every 5-10 years, and ensuring the grounding system resistance remains below the specified 10 ohms to guarantee safety and performance.
3. What key industry standards does this transmission tower comply with? Our towers are designed and manufactured in strict accordance with major international and regional standards. Key among these are IEC 60826 for loading and structural design, GB 50545 (the Chinese national standard), IEEE 738 for conductor ampacity ratings, and ASCE 10-15 for defining design loads related to wind and ice. This ensures compatibility and safety across global markets.
4. What is the purpose of the OPGW (Optical Ground Wire) at the top? The OPGW serves two critical functions. Firstly, it acts as a ground wire, shielding the primary power conductors below from direct lightning strikes by safely conducting the electrical charge to the ground. Secondly, it contains a fiber optic cable within it, providing a high-speed communication path for grid control, data acquisition (SCADA), and protective relaying, enhancing grid intelligence and reliability.
5. Can the insulator type be customized for specific environments? Yes, absolutely. While our standard configuration includes highly reliable porcelain disc insulators, we offer composite polymer insulators as a premium option. These are recommended for areas with high pollution levels, coastal regions with salt spray, or where vandalism is a concern. Their lightweight nature, at only 30% of the weight of porcelain, also simplifies installation and reduces the overall tower load.
Technical Specifications
| Tower Height | 35m |
| Voltage Rating | 110kV |
| Tower Type | Tangent (Suspension) |
| Material | Steel Lattice (Q420/Q460) |
| Number of Circuits | 2circuits |
| Conductor Bundle | 1×ACSR 240per phase |
| Design Span | 350m |
| Wind Load Design | 35m/s |
| Ice Load Design | 15mm |
| Galvanization Thickness | 85μm |
| Grounding Resistance | <10Ω |
| Design Life | 50years |
| Power Capacity per Circuit | 60-100MW |
| OPGW Fiber Count | 48-96cores |
| Foundation Type | Reinforced Concrete Pile |
| Standards Compliance | IEC 60826 / GB 50545 / IEEE 738 |
Price Breakdown
| Item | Quantity | Unit Price | Subtotal |
|---|---|---|---|
| Steel Lattice Structure (Q420/Q460, 12 tons) | 1 set | $24,000 | $24,000 |
| Hot-Dip Galvanization Treatment (12 tons) | 1 service | $5,400 | $5,400 |
| Porcelain Suspension Insulators (8-10 discs per string, 6 strings) | 54 pcs | $80 | $4,320 |
| OPGW Ground Wire (48-core fiber, per tower span) | 350 m | $15 | $5,250 |
| Grounding System (electrodes, conductors, testing) | 1 set | $2,500 | $2,500 |
| Foundation Materials (reinforced concrete pile) | 25 m³ | $350 | $8,750 |
| Hardware Fittings (clamps, shackles, bolts) | 1 set | $1,800 | $1,800 |
| Installation Labor and Equipment | 1 service | $7,200 | $7,200 |
| Total Price Range | $22,000 - $32,000 | ||
Frequently Asked Questions
What is the primary application of this 35m 110kV tangent tower?
What is the expected design life and what maintenance is required?
What key industry standards does this transmission tower comply with?
What is the purpose of the OPGW (Optical Ground Wire) at the top?
Can the insulator type be customized for specific environments?
Certifications & Standards
Data Sources & References
- •IEC 60826:2017 - Design criteria of overhead transmission lines
- •GB 50545-2010 - Code for design of 110kV-750kV overhead transmission line
- •IEEE 738-2012 - IEEE Standard for Calculating the Current-Temperature Relationship of Bare Overhead Conductors
- •ASCE Manual 10-15 - Design of Latticed Steel Transmission Structures
- •CIGRE Technical Brochure 324 - Sag-Tension Calculation Methods for Overhead Lines
Project Cases


Interested in this solution?
Contact us for a customized quote based on your specific requirements.
Contact Us